8Ć11
8.3.1 Input
P
arameters for the Masked Move Instruction
This table lists the inputs for the MVM instruction and the variable type and data
type/range that each input supports.
Parameter
Description V
ariable T
ype Data/Type Range
EN While this input is true, the instruction executes. When this
input is false, the instruction is not executed and ENO is
false.
Connect a Boolean input or output.
In Enter a constant or variable that you want to copy to Out.
In is the source of the masked move operation.
D simple
D constant
D element of an array
D integer
D double integer
D timer
(name.TPreset and
name.Elapsed)
D counter
(name.CPreset
and name.Current)
Mask Enter a variable or hexadecimal constant that specifies
which bits to pass or block. A bit set as 1 in the mask
passes the source bit into the destination. Whereas, a bit
set as 0 blocks the source bit from being copied to the
destination. See Defining a Mask" (section 8.0).
Note: Any constants entered are displayed in hexadecimal.
D simple
D element of an array
D hexadecimal
constant
D integer
D double integer
D timer
(name.TPreset and
name.Elapsed)
D counter
(name.CPreset
and name.Current)