Rockwell-automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM Instrukcja Użytkownika Strona 182

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 181
Publication AG-UM008C-EN-P - February 2005
4-44 Configuring SLC 5/03, 5/04, and 5/05 Processors
This MSG example tells the SLC 5/03, 5/04, or 5/05 master station to
write the information from its S:37 through its serial port (channel 0)
to the PLC-5 slave station 11
10
. The data’s destination is N19:0 of the
PLC-5 slave station. For a Logix slave station, a tag name would have
to already have been mapped to N19. Alternatively, SLC 5/03 (OS 302
C or higher), 5/04 (OS 401 C or higher) and 5/05 processors support
logical ASCII addressing, which means any Logix controller tag can be
written to by entering the tag name in double quotes in the Target’s
Data Table Address field.
Figure 4.7 Read MSG from an SLC 5/03, 5/04, or 5/05 Processor to a PLC-5 Processor
or Logix Controller.
MSG being sent to a
PLC-5 processor or a
Logix controller
Przeglądanie stron 181
1 2 ... 177 178 179 180 181 182 183 184 185 186 187 ... 419 420

Komentarze do niniejszej Instrukcji

Brak uwag