Navigate the Function Block Editor Interface Chapter 2
Fault State Conditions and Rules
Fault state conditions and rules are listed below.
Operation
Data Type
Condition Output Fault
Code
Fault Option
= 1
Fault
Option = 2
Fault
Option = 3
DINT The result from
the operations
ADD, SUB or
MUL exceeds
the range of the
DINT data type
Truncates Hold last
output
Value of
instance
attribute
Fault State
value
3
(Any DINT) / 0 = Dividend 3
Input data from
the binding path
is out of range
Use the
Truncates
input value
1
REAL (±) Infinity x (±)
Infinity
(±) Infinity Hold last
output
Value of
instance
attribute
Fault State
value
3
(±) Nonzero / 0 (±) Infinity 3
Infinity + Infinity Infinity 3
0 / 0 Infinity 3
Infinity - Infinity NAN 3
(±) Infinity / (±)
Infinity
NAN 3
(±) Infinity x 0 NAN 3
Sqrt ((±) Infinity) Infinity 3
0 x x 0 NAN 3
In XPY
operation,
source A is
negative while
source B is not
an integer value
NAN 3
NAN operand
for any
operation
NAN 3
Input data from
the binding path
is out of range
Use the
Truncates
input value
1