INTRODUCTION TO THE DRIVE
FlexPak 3000 49’1340 e
2-2
2.2 Drive Specifications
2.2.1 AC-Line Considerations
Requirement Measures
1) Limiting the AC line symmetrical fault
current to 100 kA (max. for fuses) or
values acc. table below for UL, cUL, as
well as limiting commutation notches at
the line input (terminals 1U, 1V, 1W).
Always adding an impedance in the line input.
This can be a 3-phase line reactor with 2%
voltage drop minimum (refer to Table 8-6) or a
matched isolation transformer.
2) Limiting the A-C line symmetrical fault
current (RMS) at the field rectifier input
(terminals 3V, 3W) to 10 kA.
Adding a 1-phase line reactor acc. to Table 8-6.
Exception: No reactor is required when a
matched transformer is provided in the input to
the converter on drives up-to 450 A.
3) Minimum supply system (source)
capacity kVA.
Connecting to a source (supply transformer) with
minimum kVA rating acc. to the following table.
4) Limiting line transformer impedance to 4%
and continuous undervoltage to 10%.
Derating of armature voltage if impedance
exceeds 4% or continuous undervoltage.
5) Avoiding damage of drive components
due to overvoltage transients caused by
medium voltage switching on supply
transformers with a primary rating of 2300
VAC or more.
Providing additional input line conditioning on the
drive (e.g. Capacitance to ground).
Please Contact Rockwell Automation for
assistance when this is required.
Minimum Source Capacity (kVA)
for different AC line voltages at 50 Hz
Full Load
Rated DC
Current
400 V 460 V 500 V 575 V 690 V
Max. Source Capacity
Symmetr. fault current (rms)
(for UL, cUL)
25 15 18 20 - - 18 kA
60 36 41 45 - - 18 kA
150 90 102 111 - - 18 kA
250 150 175 188 - - 30 kA
450 270 306 333 - - 30 kA
800 480 545 592 - - 30 kA
1200 720 818 888 - - 85 kA
1600 960 1100 1190 1400 1630 85 kA
2000 1200 1373 1486 - - 85 kA
2.2.2 Service Conditions
Standard altitude ......................................................................................up to 1000 meters
(Above 1000 m the output current must be reduced by 1% per 100m)
Standard ambient temperature at:
Operation with nominal current......................................................................0°C to 40°C
Storage ...................................................................................................... -25°C to 55°C
Transportation............................................................................................ -25°C to 70°C
Max. ambient temperature .......................................................................................... 55°C
(Above 40°C output current must be reduced by 1.5% per °C)
Relative humidity ........................................................ max 50% at 40°C unlimited time
Non-Condensating max 90% at 20°C (30 days/year)
max 75% average per year
Environment: The drive should be located in an area that is free of dust, dirt, acidic vapors,
vibration and shock, temperature extremes, and electrical or electromagnetic noise interference.
Degree of protection...................................................................................................... IP00