Rockwell-automation GV3000/SE Operator Interface Module (OIM) User Gui Instrukcja Użytkownika Strona 60

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 59
Troubleshooting the Drive Using the OIM
7-1
C
HAPTER
7
Troubleshooting the Drive
Using the OIM
Using the OIM, you can troubleshoot drive problems using one of several methods.
If a fault or alarm message is displayed, you can use the message and the Fault or
Alarm Menu to identify the problem.
If the drive is not ready, you can use the Diagnostics Menu to identify the problem.
If a program error message is displayed, you can use the message to identify the
problem.
7.1 Identifying Problems Indicated by Faults or Alarms
The OIM identifies problems as faults or alarms. A fault is a condition that stops the
drive or prevents it from running. An alarm is a condition that you should be aware of,
but it does not stop the drive or prevent it from running.
When a fault occurs:
the fault indicator turns on.
the fault is logged.
the drive coasts to a stop.
a fault message is displayed on the OIM screen, such as the one shown in figure
7.1.
!
ATTENTION:
Only qualified electrical personnel familiar with the
construction and operation of this equipment and the hazards involved
should install, operate, and/or service this equipment. Read and
understand this section in its entirety before proceeding. Failure to
observe this precaution could result in severe bodily injury or loss of life.
Figure 7.1 – Example of a Fault Screen
Przeglądanie stron 59
1 2 ... 55 56 57 58 59 60 61 62 63 64 65 ... 111 112

Komentarze do niniejszej Instrukcji

Brak uwag