ICS Regent
®
PD
-
6027
Industrial Control Services
1
Monitored Digital Input Modules, Field
Powered (Type F)
24 to 48 VDC, 120 VAC/DC
(T3411F, T3418F)
Issue 1,
March, 06
Monitored digital input modules provide input sensing for 16
field input devices. The field powered (Type F) modules are
suitable for inputs that are directly powered from an external
field power supply. Two types of modules are available for
inputs powered from 24 to 48 VDC and 120 VAC/DC. With a
line monitor device installed at the field switch, monitored
digital input modules detect input switch status and field
wiring open and short circuits (VDC powered inputs only).
Input and line status are reported back to the controller for
use in application program logic.
Features
·
Sixteen input points, powered from external field supply.
·
Fault tolerant operation when connected in parallel with
another module of the same type.
·
Hot
-
replaceable.
Complete, automatic testing of all input circuits.
Automat
ic line monitoring detects open and short field wiring
faults.
·
Individual front panel indicators on each module show the
module’s active/fault and power status, as well as input status
and line fault status for each point.
·
2500 volt minimum electrical isolation between field and logic
circuits.
·
TÜV certified, Risk Class 5.
The input module circuits are completely and automatically
tested, providing a f
ail
-
safe interface for safety
-
critical inputs.
Przeglądanie stron 0
1 2 3 4 5 6 ... 26 27

Podsumowanie treści

Strona 1 - ICS Regent

ICS Regent® PD-6027 Industrial Control Services 1 Monitored Digital Input Modules, Field Powered (Type F) 24 to 48 VDC, 120 VAC/DC (T3411F, T3418F)

Strona 2 - Module Operation

Monitored Digital Input Modules, Type F (T3411F, T3418F) 10 Industrial Control Services Figure 5. Fault Tolerant Monitored Digital Input Mod

Strona 3 - Testing and Diagnostics

Monitored Digital Input Modules, Type F (T3411F, T3418F) PD-6027 Mar-06 11 The field power supply voltage is regulated inside the module to power

Strona 4

Monitored Digital Input Modules, Type F (T3411F, T3418F) 12 Industrial Control Services Figure 6. Module Wiring, Single Sensors to a Single Mo

Strona 5

Monitored Digital Input Modules, Type F (T3411F, T3418F) PD-6027 Mar-06 13 Figure 7. Module Wiring, Single Sensors to Redundant Monitored Dig

Strona 6 - Front Panel Indicators

Monitored Digital Input Modules, Type F (T3411F, T3418F) 14 Industrial Control Services Line Monitoring For DC powered inputs, the monitored digit

Strona 7

Monitored Digital Input Modules, Type F (T3411F, T3418F) PD-6027 Mar-06 15 Figure 9 shows a single switch connected to a redundant monitored inpu

Strona 8 - Application

Monitored Digital Input Modules, Type F (T3411F, T3418F) 16 Industrial Control Services With the line monitor device installed, the input voltage,

Strona 9

Monitored Digital Input Modules, Type F (T3411F, T3418F) PD-6027 Mar-06 17 Figure 10. Installing Slot Keys. Table 2. Slot Key Positions. Mo

Strona 10 - Field Wiring

Monitored Digital Input Modules, Type F (T3411F, T3418F) 18 Industrial Control Services Configuration Each monitored input module is configured us

Strona 11

Monitored Digital Input Modules, Type F (T3411F, T3418F) PD-6027 Mar-06 19 Figure 12. Defining the Input Module Fields and Thresholds. In the m

Strona 12 - Industrial Control Services

Monitored Digital Input Modules, Type F (T3411F, T3418F) 2 Industrial Control Services Two or three monitored digital input modules can be connec

Strona 13

Monitored Digital Input Modules, Type F (T3411F, T3418F) 20 Industrial Control Services Line Monitored Input Point dialog, enter names and values

Strona 14

Monitored Digital Input Modules, Type F (T3411F, T3418F) PD-6027 Mar-06 21 Line fault status is only reported through the Fault Name variables.

Strona 15

Monitored Digital Input Modules, Type F (T3411F, T3418F) 22 Industrial Control Services short or open circuit (or there is no line monitor device

Strona 16

Monitored Digital Input Modules, Type F (T3411F, T3418F) PD-6027 Mar-06 23 represent the voted value of the two inputs. This variable would be u

Strona 17

Monitored Digital Input Modules, Type F (T3411F, T3418F) 24 Industrial Control Services the input module and performing a voted reset, the fault b

Strona 18 - Configuration

Monitored Digital Input Modules, Type F (T3411F, T3418F) PD-6027 Mar-06 25 For additional safety considerations, please refer to the Safety Consi

Strona 19

Monitored Digital Input Modules, Type F (T3411F, T3418F) 26 Industrial Control Services Input Circuit Test Interval Function of application progra

Strona 20

Monitored Digital Input Modules, Type F (T3411F, T3418F) PD-6027 Mar-06 27 Dimensions Height: Width: Depth: 12.6" (320 mm) 1.27" (3

Strona 21 - Programming

Monitored Digital Input Modules, Type F (T3411F, T3418F) PD-6027 Mar-06 3 monitored input module. The field power is internally regulated to po

Strona 22

Monitored Digital Input Modules, Type F (T3411F, T3418F) 4 Industrial Control Services The bus drivers then move the data onto the I/O Safetybus

Strona 23

Monitored Digital Input Modules, Type F (T3411F, T3418F) PD-6027 Mar-06 5 off failure modes. During testing the D/A converter generates two ref

Strona 24 - Safety Considerations

Monitored Digital Input Modules, Type F (T3411F, T3418F) 6 Industrial Control Services Front Panel Indicators Figure 2 shows the physical feature

Strona 25 - Specifications

Monitored Digital Input Modules, Type F (T3411F, T3418F) PD-6027 Mar-06 7 Figure 2. Type F, Monitored Digital Input Modules.

Strona 26

Monitored Digital Input Modules, Type F (T3411F, T3418F) 8 Industrial Control Services Application Simplex Configuration Monitored digital input

Strona 27

Monitored Digital Input Modules, Type F (T3411F, T3418F) PD-6027 Mar-06 9 Figure 4. Fault Tolerant Monitored Digital Input Modules Connect

Komentarze do niniejszej Instrukcji

Brak uwag