ICS Regent
®
PD
-
6023
Industrial Control Services
1
Analog Input Modules
60 Hz Rejection and Fast Response
(T3420A and T3420AF)
Issue 1,
March, 06
Analog input modules provide data input for a maximum of
16 field analog signals per module. Two types of modules are
available: one for high noise immunity (60 Hz rejection) and
one with low noise immunity (fast response).
Features
·
Sixteen single
-
ended or eight differential
voltage
inputs.
Interface to current
inputs using external 250 ohm resistors for
current to voltage conversion (resistors are provided as part of
the analog input termination blocks, catalog number T3325
-
XX).
·
Fault tolerant operation when connected in parallel with
redundant modules of the same type.
·
Hot replaceable.
·
Jumper
-
selectable input ranges.
·
12
-
bit analog to digital resolution (1 part in 4096).
·
Sample rate of all channels in 1.8 msec (differential) or 3.6
msec (single
-
ended).
·
60 Hz rejection (T3420A) and fast response (T3420AF)
versions available.
·
2500 volt isolation between analog and digital log
ic cir
cuits.
·
Individual front panel indicators on each module show module
active and fault status.
·
TÜV certified for safety, Risk Class 5.
Each module’s triplicated I/O Safetybus interface ensures that
no failure in the module can affect the operation of the Regent
system or other I/O modules in the system. Extensive fault
detection and annunciation of critical redundant circuits help
Przeglądanie stron 0
1 2 3 4 5 6 ... 38 39

Podsumowanie treści

Strona 1 - ICS Regent

ICS Regent® PD-6023 Industrial Control Services 1 Analog Input Modules 60 Hz Rejection and Fast Response (T3420A and T3420AF) Issue 1, March, 06 An

Strona 2 - Module Operation

Analog Input Modules (T3420A, AF) 10 Industrial Control Services In differential mode, a 10K Ohm resistor is in series with each input line of eac

Strona 3 - Testing and Diagnostics

Analog Input Modules (T3420A, AF) PD-6023 Mar-06 11 Figure 4. Analog Input Configuration Jumper Locations.

Strona 4 - Front Panel Indicators

Analog Input Modules (T3420A, AF) 12 Industrial Control Services Simplex Configuration Analog input modules provide a suitable interface to non-cr

Strona 5

Analog Input Modules (T3420A, AF) PD-6023 Mar-06 13 Figure 6. Fault Tolerant Analog Input Configurations. Field Wiring Field wiring termina

Strona 6 - Application

Analog Input Modules (T3420A, AF) 14 Industrial Control Services transmitters (that require loop power) you will typically need to connect a 24 VD

Strona 7

Analog Input Modules (T3420A, AF) PD-6023 Mar-06 15 Figure 7. Module Wiring (Single-Ended).

Strona 8

Analog Input Modules (T3420A, AF) 16 Industrial Control Services Figure 8. Module Wiring (Differential).

Strona 9 - Pass Filters

Analog Input Modules (T3420A, AF) PD-6023 Mar-06 17 Analog Input Termination Blocks Optional analog input termination blocks can serve as the fie

Strona 10 - Industrial Control Services

Analog Input Modules (T3420A, AF) 18 Industrial Control Services A 1K Ohm resistor isolates the grounding terminal on the input termination block

Strona 11

Analog Input Modules (T3420A, AF) PD-6023 Mar-06 19 Figure 10. Single-Ended Voltage Input Wiring.

Strona 12 - Fault Tolerant Configurations

Analog Input Modules (T3420A, AF) 2 Industrial Control Services prevent the controllers from receiving erroneous data from a faulty input module.

Strona 13 - Field Wiring

Analog Input Modules (T3420A, AF) 20 Industrial Control Services Figure 11. Differential Voltage Input Wiring.

Strona 14

Analog Input Modules (T3420A, AF) PD-6023 Mar-06 21 Single-Ended Current Mode Input Termination Block Sets (T3325-S and -SJ) These input terminat

Strona 15

Analog Input Modules (T3420A, AF) 22 Industrial Control Services Figure 12. Single-Ended Current Input Wiring.

Strona 16

Analog Input Modules (T3420A, AF) PD-6023 Mar-06 23 Figure 13. Differential Current Input Wiring.

Strona 17

Analog Input Modules (T3420A, AF) 24 Industrial Control Services Keying The I/O chassis can be physically keyed to prevent accidental damage cause

Strona 18

Analog Input Modules (T3420A, AF) PD-6023 Mar-06 25 Table 5. Slot Key Positions. Module Upper Connector Lower Connector T3420A 9 15 T3420AF 9 15

Strona 19

Analog Input Modules (T3420A, AF) 26 Industrial Control Services Figure 15. Analog Input Module Definition. 3) Edit each point: Position the cu

Strona 20

Analog Input Modules (T3420A, AF) PD-6023 Mar-06 27 often you will want to scale the analog input values to a more convenient engineering unit nu

Strona 21

Analog Input Modules (T3420A, AF) 28 Industrial Control Services Programming Fault Tolerant Analog Inputs To program fault tolerant configurations

Strona 22

Analog Input Modules (T3420A, AF) PD-6023 Mar-06 29 help you determine the frequency for checking the calibration of the modules in your installa

Strona 23

Analog Input Modules (T3420A, AF) PD-6023 Mar-06 3 The processor modules send triplicated read data requests to the analog input module over the

Strona 24

Analog Input Modules (T3420A, AF) 30 Industrial Control Services Calibration Preparation The module must be calibrated while connected to an I/O c

Strona 25 - Configuration

Analog Input Modules (T3420A, AF) PD-6023 Mar-06 31 Figure 19. Analog Input Module Calibration Potentiometer Locations. The I/O extender modu

Strona 26 - Programming

Analog Input Modules (T3420A, AF) 32 Industrial Control Services Figure 20. I/O Extender Connections for Single-Ended Analog Input Calibration

Strona 27

Analog Input Modules (T3420A, AF) PD-6023 Mar-06 33 Figure 21. I/O Extender Connections for Differential Analog Input Calibration. Within eac

Strona 28 - Maintenance

Analog Input Modules (T3420A, AF) 34 Industrial Control Services 4. Connect the DC voltage signal source to the I/O extender jumper posts as shown

Strona 29 - Calibration Procedure

Analog Input Modules (T3420A, AF) PD-6023 Mar-06 35 clamshell housing. Remove the I/O extender module from the I/O chassis and reinstall the cal

Strona 30 - Important!

Analog Input Modules (T3420A, AF) 36 Industrial Control Services Specifications Safetybus Power 1.85 load units Number of Inputs Eight differentia

Strona 31

Analog Input Modules (T3420A, AF) PD-6023 Mar-06 37 Out of Range Thresholds Over-range -10.00 to +10.00 volts: 0.00 to +10.00 volts: -5.00 t

Strona 32

Analog Input Modules (T3420A, AF) 38 Industrial Control Services Operating Temperature 0° to 60° C (32° to 140° F) Storage Temperature -40° to 85°

Strona 33

Analog Input Modules (T3420A, AF) PD-6023 Mar-06 39 Miscellaneous Input Circuit Specifications Function Signal Mode Value I leakage AI1 through A

Strona 34

Analog Input Modules (T3420A, AF) 4 Industrial Control Services produces an I/O module error indication at the processor modules and a module fau

Strona 35 - Safety Considerations

Analog Input Modules (T3420A, AF) PD-6023 Mar-06 5 Figure 3. Analog Input Module.

Strona 36 - Specifications

Analog Input Modules (T3420A, AF) 6 Industrial Control Services Application Analog Input Range Selection The possible input voltage ranges are th

Strona 37

Analog Input Modules (T3420A, AF) PD-6023 Mar-06 7 Sampling Speed The rate at which each of the analog input channels is sampled depends upon th

Strona 38

Analog Input Modules (T3420A, AF) 8 Industrial Control Services Input Over Voltage Protection All analog inputs, regardless of mode and analog re

Strona 39

Analog Input Modules (T3420A, AF) PD-6023 Mar-06 9 Table 2. Mode Selection. Jumper Single-Ended Differential J251 n J252 n J501 n J502 n J5