(T3464)
AC Guarded Digital Output Module
PD
-
6021
Mar
-
06
21
1 amp maximum per output
0°
to 40
°
C, derated linearly
to 0.5 amp at 60
°
C
16 amps maximum per
module at 0
°
C, derated
linearly to 8 amps at 60
°
C
Load Current (minimum)
Guarded mode:
Fault tolerant mode:
Load current plus 16 amps
transient during crowbar
actuation
16 amps maximum transient
during crowbar actuation
Output Leakage
Guarded mode:
Fault tole
rant mode:
5 mA maximum at 60 Hz
10 mA maximum at 60 Hz
One 2 A, 250 V, fast acting
(3AG) per output, front panel
mounted
70 V peak for 1.1 msec,
3
pulses, repeating once per
2 seconds.
130 VAC for 200 msec, one
-
time for shorted output
circuit