ICS Regent+Plus
®
PD
-
7016
Industrial Control Services
1
AC Digital Output Module
110 VAC
(T7444)
Issue 1,
March, 06
The AC digital output module provides control of 16 user
output loads. One type of module is available to interface to
outputs powered from a nominal 110 VAC field power su
pply.
Each module's triplicated I/O Safetybus interface ensures that
no Regent system failure can incorrectly apply power to an
output, and that no failure in the module can affect the
operation of the Regent system or other I/O modules in the
system.
Features
·
Sixteen output circuits, configured as two isolated groups of
eight circuits each.
·
Hot
-
replaceable.
·
Automatic self
-
testing of triplicated I/O Safetybus circuits and
many simplex logic circuits.
·
2 amp output circuits.
·
Zero
-
cross load switching.
·
Individual front panel indicators on each module show active
and fault, shutdown, blown fuse, and output on/off status (logic
side).
·
2500 volt minimum electrical isolation between field and logic
circuits.
·
Fuses accessible from front panel.
·
TÜV certified, Risk Class 5, non
-
interfering.
Przeglądanie stron 0
1 2 3 4 5 6 ... 12 13

Podsumowanie treści

Strona 1 - ICS Regent+Plus

ICS Regent+Plus® PD-7016 Industrial Control Services 1 AC Digital Output Module 110 VAC (T7444) Issue 1, March, 06 The AC digital output module pro

Strona 2 - Module Operation

AC Digital Output Module (T7444) 10 Industrial Control Services Name Also called the tag name, this is the name used in the application program to

Strona 3 - Front Panel

(T7444) AC Digital Output Module PD-7016 Mar-06 11 control logic by using a contact element (or similar element) with the output point name. Main

Strona 4 - Industrial Control Services

AC Digital Output Module (T7444) 12 Industrial Control Services Specifications Safetybus Power 0.8 load units Number of Outputs 16 circuits divide

Strona 5

(T7444) AC Digital Output Module PD-7016 Mar-06 13 Operating Humidity 0 to 95% relative humidity, non-condensing Vibration 10 to 55 Hz: ±0.15mm

Strona 6 - Application

AC Digital Output Module (T7444) 2 Industrial Control Services Module Operation A block diagram of a typical 110 VAC digital output module is sho

Strona 7 - Fault Mode Jumper

(T7444) AC Digital Output Module PD-7016 Mar-06 3 Optical isolation between the module’s logic and field circuits provides logic-to-field isolat

Strona 8 - Configuration

AC Digital Output Module (T7444) 4 Industrial Control Services Active and Fault Status Indicators These green and red LEDs indicate the overall h

Strona 9

(T7444) AC Digital Output Module PD-7016 Mar-06 5 Figure 2. 110 VAC Digital Output Module.

Strona 10 - Programming

AC Digital Output Module (T7444) 6 Industrial Control Services Application Simplex Configuration Digital output modules provide a suitable interf

Strona 11 - Safety Considerations

(T7444) AC Digital Output Module PD-7016 Mar-06 7 Fault Mode Jumper The fault mode jumper is located behind the ID switch cover in the lower le

Strona 12 - Specifications

AC Digital Output Module (T7444) 8 Industrial Control Services Figure 4. Installing Slot Keys. Configuration Each output module is configured

Strona 13

(T7444) AC Digital Output Module PD-7016 Mar-06 9 1) Set the Module Type: Position the cursor on the module slot you wish to define. Choose Se