AC Isolated Digital Output Module
PD
-
7018
Mar
-
06
7
Fault Mode
Jumper
The fault mode jumper is located behind the ID switch cover
in the lower left
-
hand corner of each I/O chassis. The position
of the fault mode jumper determines the module's response to
system level faults. The fault mode jumper’s position will
cause all output modules in the I/O chassis to either shutdown
(turn off all outputs) or to hold (hold the last state) after a
system level failure occurs. An example of a system level
failure is the failure of two processor modules.
Keying
The I/O chassis
can be physically keyed to prevent accidental
damage caused by inserting a module into a slot wired for a
different module type. Figure
4
illustrates how the slot keys
are installed on the I/O chassis slot field wiring connectors.
The slot key positions for the AC isolated digital output
module are listed in Table
1
.
Table
1
. Slot Key Positions.
Module
Upper
Connector
Lower
Connector
T7454
16
2