Supported Emulated Block Transfer Commands F-5
Figure F.3 Parameter Value Write Message Structure
Message Operation
Parameter Value Write sends a new value to the specified parameter.
The value must be in device units. Units for each parameter are listed in
the device manual.
If an error has occurred, word 1 of the response returns a value of
–31999, and word 3 contains a status code.
Example
In this example, a value of 4096 was sent to Parameter 20. 4096 is in
drive units and indicates a value of 100% Drive Rated Volts, as defined
in P147, Drive Rated Volts.
Data File Format
* Example only — These values vary depending on parameters and products.
Header Word 1
Data Word 2
PLC Request
Message Length
PLC Decimal Value
–31999
Parameter Number
Drive Response
4
Data Word 3Parameter Data
Header
Word 0
Header
Word 1
Data
Word 2
Message Length
PLC Decimal Value
769 — Message OK
–31999 — Message Error
Parameter Number
3 or 4
Data
Word 3
Status Word
Header Word 0
01 23456789
PLC request 4 –31999 20* 4096*
Drive response 376920*