Rockwell-automation 1203-EN1 EtherNet/IP-to-SCANport Module Instrukcja Użytkownika Strona 30

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 29
3-4 Configuring the Module
The New Entry dialog box appears.
Figure 3.3 New Entry Dialog Box
4. Enter in the following data:
5. Click OK to apply the settings. The module appears in the Relation
List with the new settings.
Figure 3.4 BOOTP Server Window with a Module in the Relation List
6. To assign this configuration to the module permanently, click
Disable BOOTP. When power is cycled on the module, it will use
the configuration you assigned it and not issue new BOOTP requests.
7. To save the Relation List, select File > Save.
Box
(1)
(1)
For definitions, refer to the Glossary.
Type
IP Address A unique IP address for the module
Subnet Mask The subnet mask for the module’s network
Gateway The IP address of the gateway device on the module’s network
TIP: To enable BOOTP for an module that has had BOOTP
disabled, first select the module in the Relation List (add if
necessary), then click Enable BOOTP, and finally reset the
module.
Przeglądanie stron 29
1 2 ... 25 26 27 28 29 30 31 32 33 34 35 ... 185 186

Komentarze do niniejszej Instrukcji

Brak uwag