Chapter 3
General Operation
3–10
Discrete Outputs (From the PLC Processor)
The following discrete output control signals will be provided from the
PLC–5 processor via the back plane:
Initiate Synchronization
Auto–Synchronization Mode
Check Synchronization Mode
Permissive Synchronization Mode
Load Share Disable
Isochronous/Droop Mode
Enable Single Phase Synchronization
Discrete Inputs (To the PLC Processor)
The following discrete input control signals will be provided to the PLC–5
processor via the back plane:
Module Status
Raise Voltage
Lower Voltage
Raise Speed –– frequency adjust
Lower Speed –– frequency adjust
Raise Speed –– phase adjust
Lower Speed –– phase adjust
Raise Power –– load share adjust
Reduce Power –– load share adjust
Close Breaker
Synchronization Failure
Power–up Bit
Block Transfer Data Interface
The LSM is capable of exchanging large amounts of data with the PLC
processor via the Block Transfer mechanism. The amount of data greatly
exceeds that which could be accommodated by a single block transfer. As a
result, the data is divided into several different “files” and can be obtained
through the use of multiple Block Transfers. The sizes, structure, and
contents of the block transfer reads and writes supported by the LSM are
provided in Appendix B. See “Block Transfer Communications”, listed on
Page 4–2 in the Application Information chapter of this manual for further
details on using Block Transfers.
PLC Interface Continued
Przeglądanie stron 31
1 2 ... 27 28 29 30 31 32 33 34 35 36 37 ... 86 87

Komentarze do niniejszej Instrukcji

Brak uwag