Chapter 1
Product Description
1–2
In order to synchronize two three phase systems without high instantaneous
energy transfer, the voltage, frequency, and phase displacement of the two
systems must be matched. Kilowatt Load Sharing can be implemented by
matching the ratio of power system load to system capacity to the ratio of
actual alternator power to rated alternator power. The LSM provides the
following information to allow the users system to achieve the necessary
control actions.
Voltage Match Error (in steps of 0.05 percent)
Frequency Match Error, or slip (in steps of 0.01 Hz)
Synchronizing Bus to Reference Bus Phase Match Error (in steps of 1
degree)
Load Sharing Error (scalar quantity between 0.000 and 1.000)
Synchronization Status
Frequency Within Limits
Voltage Within Limits
Phase Within Limits
Synchronization Mode Conflict Failure
Phase Rotation Mismatch Failure (3 phase synchronization mode only)
No Reference Bus Voltage Present Failure
No Synchronizing Bus Voltage Present Failure
Reference Bus Over Voltage Failure
Synchronizing Bus Over Voltage Failure
Synchronization and
Load Share Errors