Rockwell-automation 140U H-Frame Circuit Breaker Fixed and Adjustable Instrukcja Użytkownika Strona 2

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 2
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 1
Effective 01/01
4
5
3
10 in-lb (0.2 Nm)
34-38 in-lb (3.8-4.3 Nm)
10 in-lb (0.2 Nm)
ON
TRIP
OFF
RESET
Push to trip
6
Warning
INSTALL WIRE APPLICABLE
TO THE HIGHEST RATING
SHOWN ON BREAKER.
Note: Mounting hardware included. Use nuts (provided)
if not threading holes in mounting surface.
Note: Endcap is sold separately.
Optional thermal adjustment
H Frame Collar Torque Values
Wire Size Torque
AWG (mm
2
) In-lb
(N
m)
14-10 (2.5-6) 35 (4.0)
8 (10) 40 (4.5)
6-4 (16-25) 45 (5.1)
3-3/0 (35-95) 50 (5.6)
Note: If cover must be
removed for accessory
installation, torque
cover mounting screws
to 6-8 in-lb (.7-.9 N
m).
40752-001
Effective 02/02
Przeglądanie stron 1
1 2

Komentarze do niniejszej Instrukcji

Brak uwag