13 Publication 1732E-UM002A-EN-P - March 2010
Chapter
4
Install Your Module
Overview
This chapter shows you how to install and wire the 1732E EtherNet/IP
ArmorBlock Supporting Sequence of Events. The only tools you require are a
flat or Phillips head screwdriver and drill.
Mount the Module
To mount the module on a wall or panel, use the screw holes provided in the
module.
Refer to the drilling dimensions illustration to guide you in mounting the
module.
Install the mounting base as follows:
1. Lay out the required points as shown above in the drilling dimension
drawing.
2. Drill the necessary holes for #8 (M4) pan head screws.
3. Mount the module using #8 (M4) screws.
44946
179 mm
(7.05 in.)
169 mm
(6.64 in.)
65 mm
(2.56 in.)
43.25 mm
(1.70 in.)
26.5 mm
(1.04 in.)
Front view
Side view
32.5 mm
(1.28 in.)