14 POINT I/O Module with 8 Configurable 24V DC Points and DeviceLogix
Publication
1734-IN039A-EN-P - March 2009
You can select other produced assemblies:
• Produced assembly instance 4 is the first byte of produced assembly
instance 101 (Data [0]).
• Produced assembly instance 111 is the first eight bytes of produced
assembly instance 101 (Data [0]…[7]).
In RSLogix5000, the default tags will be:
• AdapterName:SlotNumber:I.Data
• AdapterName:SlotNumber:I.LogicDefinedData
• AdapterName:SlotNumber:I.Status.LogicEnabled
• AdapterName:SlotNumber:I.Status.Owned
• AdapterName:SlotNumber:I.PeerMissing
• AdapterName:SlotNumber:I.LogicDefinedIntData[0...7]
Data [16] Produce Network Analog Word 6
Data [17]
Data [18] Produce Network Analog Word 7
Data [19]
Where:
• Pt = state of the output point,
• PNB = Produce Network Bit,
• PM = Peer Missing (each bit represents the presence of a configured peer)
• Owned = Owned by a master.
When set to 0, the module is producing data without a master.
When set to 1, the module is producing while being owned by a master.
• LogicEn = Logic Enabled (0 = logic disabled, 1 = logic enabled)
Default Data Map - Produced Assembly Instance 101 (Continued)
Message Size: 20 Bytes