POINT I/O 120V AC Input Module 17
Publication 1734-IN010D-EN-E - March 2013
Interpret Status Indicators
Refer to the following diagram and table for information on how to interpret the
status indicators.
Indicator Status for Modules
Status Description Recommended Action
Module status Off No power applied to device. Apply power to device.
Green Device operating normally. None.
Flashing green Device needs commissioning
due to missing, incomplete, or
incorrect configuration.
Configure device properly.
Flashing red Recoverable fault. Cycle power to device. If
condition persists, replace
device.
Red Unrecoverable fault – may
require device replacement.
Replace device.
Flashing red/green Device is in self-test mode. None.
1734-IA2
44214
Module status
Network status
Status of Input 1
1734-IA4
Status of Input 2
Status of Input 3
44215
Module status
Network status
Status of Input 0
Status of Input 1
Status of Input 0