POINT I/O 120/220V AC Output Module 17
Publication 1734-IN009E-EN-E - March 2013
Indicator Status for Modules
Status Description Recommended Action
Module status Off No power applied to device. Apply power to device.
Green Device operating normally. None.
Flashing green Device needs commissioning
due to missing, incomplete, or
incorrect configuration.
Configure device properly.
Flashing red Recoverable fault. 1. Cycle power to device.
2. If condition persists, replace
device.
Red Unrecoverable fault – may
require device replacement.
Replace device.
Flashing red/green Device is in self-test mode. None.
Network status Off Device is not online:
- Device has not completed
dup_MAC-id test.
- Device not powered – check
module status indicator.
Apply power to device, wait for
MAC_id to complete and correct
as needed.
Flashing green Device is online but has no
connections in the established
state.
None – device is in Idle or
Program mode.
Green Device is online and has
connections in the established
state.
None.
Flashing red One or more I/O connections are
in timed-out state.
Check for I/O module failure and
correct as needed.
Red Critical link failure – failed
communication device. Device
detected error that prevents it
from communicating on the
network.
Verify that adapter and terminal
bases are properly installed and
reinstall as needed.
Flashing red/green Communication faulted device –
the device has detected a
network access error and is in
communication faulted state.
Device has received and
accepted an Identity
Communication Faulted Request
– long protocol message.
Verify that adapter is properly
installed and reinstall as
needed.
I/O status Off All outputs inactive. None.
Yellow One or more outputs are active
and under control.
None.