Single-Ended Wiring (Discrete Devices)
(1) External resistors are needed if not internal to the sensor. Check your sensors documentation.
The pull-up resistor (R) value depends on the power supply value. The table below shows
resistor values for typical supply voltages. To calculate the resistor value, use one of the
following formulas:
For 5V dc:
For 24V dc:
where:R = pull-up resistor value
Vcc = power supply voltage
Vmin = 4.2 V dc
Imin = 6.3 mA
Power Supply Voltage (Vcc)
Pull-up Resistor Value (R)
(1)
(1) Resistance values may change, depending upon your application.
5V dc 127
12V dc 238
24V dc 2140
VS
A(+)
A(–)
B(+)
B(–)
Z(+)
Z(–)
+VDC
COM
VS
OUT
COM
OUT
COM
VS
OUT
COM
R
(1)
Power
Supply
proximity sensor
photoelectric sensor
with open collector
sinking output
Module Inputs
solid-state
switch
R
Vcc Vmin
()
Imin
------------------------------------=
R
Vcc Vmin
()
Imin