Chapter
4
Configuration and Programming
This chapter provides information about:
selecting operating class
module programming
programming blocks
programming block default values
Selecting Operating Class
The 1746-HSCE2 module has two operating classes which are
determined by the ID code used by the module.
Class 1 operation uses 8 input and 8 output words and is compatible
with SLC 5/01 and above processors and the 1747-ASB module. Enter
ID Code 3511 to select Class 1 operation.
Class 4 operation uses 23 input and 8 output words and is compatible
with SLC 5/03 and above processors and with 1747-ACN15 and
-ACNR15 modules. Enter ID Code 15912 to select Class 4 operation.
See Operating Class on page 1-4 for more information on Class 1 and
Class 4 operation.
Power-up Reset
Whenever power is cycled or the processor mode is switched to RUN,
all counters are reset to their defaults. The counters, ranges, presets,
etc., need to be reprogrammed. See the default settings on page 4-28.
Module Programming
Module programming consists of the following six blocks:
Module Setup
Counter Configuration
Minimum/Maximum Count Value
Minimum/Maximum Rate Value
Program Ranges
Counter Control