Publication 1746-UM002B-EN-P - August 2004
4-20 Configuration and Programming
Figure 4.8 Program Ranges Block
Programming Block Identification Bit
(Word 0, Bit 04)
This bit identifies the type of block.
TRMT: Transmit Bit
(Word 0, Bit 15)
A 0 to 1 transition starts a programming cycle.
DEBUG: Debug Mode Selection Bit
(Word 0, bit 12)
When this bit is set, the debug mode is activated. Debug mode returns
the input data file showing current settings in the Program Ranges
block. For details, see Debug Mode Operation on page 5-7.
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word 0
TRMT
0 0
DEBUG
0
RType
CNTR
No
0 0 010 0 0 0
Word 1 Range Number
Word 2
Range Start Value
Word 3
Word 4
Range Stop Value
Word 5
Word 6
0 0 0 0 0 0 0 0
Output State
Virtual Real
Word 7
RESERVED: Must equal zero