By default, outputs in all slots in the remote chassis are reset if the processor is
placed into the Pr ogram mode or if communications are lost for any reason.
Two other choices are offered when one of the two conditions occur. They
are:
Hold Last Outputs
Outputs to Safe State
Hold Last Outputs holds outputs in their last state if one of the two conditions
occur. Safe State allows you to choose the exact state of each output. If Safe
State is selected, you must click on the Configuration Settings tab and enter you
Safe State data for each output word in decimal. Then, if the SLC processor is
placed in the Pr ogram mode or if communications are lost to the ACN adapter,
the outputs revert to the Safe State data you entered for each output word.