Rockwell-automation 1747-ACNR15 ControlNet Adapter Module User Manual Instrukcja Użytkownika Strona 68

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 67
Publication 1747-UM003A-EN-P
4-40
By default, the Chunk 1 Output File is the output image file for the Basic
module and the Chunk 1 Input File is the input image file for the Basic
module. You must then assign the Chunk 2 Output File as the Basic modules
M0 file and the Chunk 2 Input File as the Basic modules M1 file.
The size for each of these files is 64 words. The total number of words
transferred bi-directionally between the SLC processor and the Basic module
will be 72. The first 8 will be the Basic modules I/O image and the last 64
words will be the Basic module’s M-file words. This order is determined by the
Chunk numbers. The Advanced screen should then look like the following:
Przeglądanie stron 67
1 2 ... 63 64 65 66 67 68 69 70 71 72 73 ... 139 140

Komentarze do niniejszej Instrukcji

Brak uwag