6-50 Library of Routines
OC_ReadModuleFile
OC_ReadModuleFile reads a data file from a module.
Syntax:
int OC_ReadModuleFile(HANDLE handle, BYTE ftype,
WORD *mfile, int slotnum, WORD offset, WORD len);
Parameters:
Description:
This function accesses an internal data file of the selected module. I/O
scanning is blocked while this access takes place.
Return Value:
Considerations:
Supported in the DOS API library and the Windows NT API library
Parameter: Description:
handle Must be a valid handle returned from OC_OpenScanner
ftype Defines the module type as:
FILTYP_M0 M0 file
FILTYP_M1 M1 file
FILTYP_G G file
mfile Buffer file that contains data read from the module at
slotnum
The data in mfile is read from the module starting at word
offset. This function does not read data past the end of the
module file for the slot.
slotnum Must be a valid slot number
offset Must be valid word number within module file
len Number of words read from the module located at
slotnum on the
scanner into the buffer
mfile
Name: Value: Description:
SUCCESS 0 file was read successfully
ERR_OCACCESS 2
handle does not have access to scanner
ERR_OCPARAM 8 parameter contains invalid value
ERR_OCRESPONSE 10 scanner did not respond to request
ERR_OCSCANCFG 14 scanner has not been configured
ERR_OCSLOT 12 slot number is invalid