5-2 Configuring I/O Modules
SlotCfg contains information about each slot in the racks. The 1746
I/O PCI Interface supports as many as 31 slots, numbered 0 to 30. Slot
0 is the adapter slot (left slot of rack 1) and is invalid for scanner
functions. Each slot is described by the structure
OCSLOTCFG:
struct {
BYTE mix; /* Module I/O Mix value */
BYTE type; /* Module Type */
BYTE InputSize; /* number of inputs in bytes */
BYTE OutputSize; /* number of outputs in bytes */
WORD M0Size; /* size of M0 file in words */
WORD M1Size; /* size of M1 file in words */
WORD GSize; /* size of G file in words */
WORD *GData; /* pointer to array of length GSize
words */
char *Name; /* pointer to module name string */
} OCSLOTCFG;
You can specify a module by name or by mix and type. You only
specify G data if the module uses G files (such as the 1747-SN). If the
Name pointer is NULL, OC_CreateIOConfiguration uses mix and type
to identify the module. See page 4 for the
mix and type values.
OC_CreateIOConfiguration supplies the
InputSize, OutputSize,
M0Size, M1Size, Gsize, and Name fields.
If
Name points to a string containing a valid module name, the module
name identifies the module. OC_CreateIOConfiguration supplies the
mix, type, InputSize, OutputSize, M0Size, M1Size, and Gsize
fields.
Initialize empty slots and slot 0 with a
mix value of 0xFF and a type
value of 0xFF.
If the module is not in the internal database,
OC_CreateIOConfiguration doesn’t alter the OCSLOTCFG.
To support modules not included in the internal database of modules,
the host application can initialize the
mix, type, InputSize,
OutputSize, M0Size, M1Size, and GSize before downloading the
I/O configuration to the scanner. See the I/O module’s user manual to
determine the proper configuration information.
After the OC_CreateIOConfiguration and OCGetIOConfiguration
functions return, the I/O configuration structure must be checked for
installed modules with G files. If the Gsize field of a non-empty slot
configuration is not zero, then the module contains a G file. If the
module contains a G file, initialize GData to point to an array of
Gsize words to be loaded into the module during scanner
configuration. See the I/O module’s user manual to determine the
proper G file data.