Rockwell-automation 1756-CN2R ControlLogix ControlNet Interface Module Instrukcja Użytkownika Strona 27

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 32
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 26
ControlLogix ControlNet Bridge Module 27
Publication
1756-IN602A-EN-P - November 2005
Radiated RF immunity IEC 61000-4-3:
10 V/m with 1 kHz sine-wave 80%AM from 30…2000 MHz
10 V/m with 200 Hz 50% Pulse 100%AM at 900 MHz
10 V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz
1 V/m with 1 kHz sine-wave 80%AM from 2000 MHz…2700 MHz
EFT/B immunity IEC 61000-4-4:
±2 kV at 5 kHz on communications ports
Surge transient immunity IEC 61000-4-5:
±2 kV line-earth(CM) on communications ports
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz
Enclosure type rating None (open-style)
Environmental Specifications
Attribute Value