26 EtherNet/IP Web Server Module
Publication
1756-IN588A-EN-P - February 2004
Link Status Indicator
The Link Status LED provides the following information:
OK Status Indicator
The OK Status LED provides the following module information:
Where to Find More Information on Configuring the Module
For more details on configuring your web server module, refer to the
EtherNet/IP Web Server Module User Manual, publication ENET-UM527A.
State Status Description
Off No data transmission Module is not ready to communicate.
Green Ready Module is ready to communicate.
Flashing Green Data transmission in
progress
Module is communicating over the
network.
State Status Description
Off No Power Module does not have 24V DC power.
Verify there is chassis power and the
module is completely inserted into
chassis and backplane.
Flashing Green Standby Module is not configured.
Green Operational Module is operating correctly.
Flashing Red Minor Fault A recoverable fault has been detected.
This could be caused by an error in the
configuration.
Red Major Fault An unrecoverable fault has been
detected. Recycle power to the module.
If this does not clear the fault, replace
the module.
Flashing Red and Green Self Test Module performing power-up self-test.