146 Rockwell Automation Publication 1769-UM006E-EN-P - July 2013
Appendix C Program a 1769-HSC Module, MicroLogix 1500 Controller, and 845F Incremental Encoder with RSLogix 500 Software
Your Counter tab should look like the example below.
4. Click the Ranges tab to display the counter range configuration window
with default values.
5. Use this information to complete the configuration for the Ranges tab.
6. Click OK.
Option Value
Range #0 Range #1
Counter Used Counter #0 Counter #0
Range Type Count Value Count Value
High Limit 600,000 1,200,000
Low Limit 500,000 1,000,000
Range Active Within the Limits Within the Limits
Output Mask 0001 0002