16 Compact™ 1769-OF2 (Series B or Later) Analog Output Module
Publication 1769-IN049A-EN-P
Channel Configuration Words
Words 0 through 1 of the configuration file allow you to change the
parameters of each channel independently. For example, word 0
corresponds to channel 0.
Define These bit settings Indicate this
15 14 13 12 11 1098 4-7 3210
Program
(Idle) to
Fault
Enable
Not Used
Not Used
0 Program (Idle) Mode
Data Applied
(1)
(1) These functions are not supported by all controllers (e.g. MicroLogix 1500) using any configuration method.
Refer to your controller manual for details.
1 Fault Mode Data
Applied
(1)
Not Used (Reserved)
Program
(Idle) Mode
0
Hold Last State
(1)
1 User-Defined
Value
(1)
Fault Mode 0
Hold Last State
(1)
1 User-Defined Fault
Value
(1)
Output
Range
Select
0000 -10V dc to +10V dc
0001 0 to 5V dc
0010 0 to 10V dc
0011 4 to 20 mA
0100 1 to 5V dc
0101 0 to 20 mA
Spare
(2)
(2) Any attempt to write a non-valid (spare) bit configuration into any selection field results in a module
configuration error.
Output
Data
Select
000 Raw/Proportional
Data
001 Engineering Units
010 Scaled-for-PID
011 Percent Range
Spare
(2)
Enable
Channel
1 Enabled
0
Disabled