Compact™ 16-Point AC/DC Relay Output Module 11
Publication 1769-IN062A-EN-P - December 2001
I/O Memory Mapping
Output Data File
Data output bits are turned on or off using the bit positions in Word 0.
1 = output on
0 = output off
Example: To turn on bit position 12, type 1 in Word 0, Bit 12.
For each module, slot x, word 0 in the output data file contains the control
program’s directed state of the discrete output points.
w = write only
Output Module’s Input Data File
For each module, slot x, input data file word 0 contains the state of the module’s
output data (output data echo) file word 0. During normal operation, these input
bits represent the logic state that the outputs are directed to by the control program.
They are also dependent upon the:
Program Mode configuration (if supported by the controller)
The Fault Mode configuration (if supported by the controller).
r = read only
Word
Bit Position
1514131211109876543210
0wwwwwwwwwwwwwwww
Word
Bit Position
1514131211109876543210
0rrrrrrrrrrrrrrrr
IMPORTANT
The output module’s input data file reflects the output data echo
of the module, not necessarily the electrical state of the output
terminals. It does not reflect shorted or open outputs.
It is important to use this input word if the controller adapter
supports the Program Mode or Fault Mode function, and if it is
configured to use them.