Installing the Linear Positioning Module
Chapter 5
520
The two discrete outputs for each loop are powered by the discrete output power
supply. The characteristics of the discrete outputs are:
Low no voltage applied to the output
High output supply voltage applied to output
Maximum Current 100 mA
Voltage Drop 1.6 VDC maximum (at 100 mA) between the dis
crete output power supply (terminal 40) and the
discrete outputs
Power for the OUTOUT 1 and OUTPUT 2 discrete outputs comes from the
discrete output power supply through terminal 40 on the module wiring arm.
The return for the load driven by OUTOUT 1 or OUTPUT 2 connects to the
common of the discrete output power supply.
Figure 5.12 shows a typical discrete output connection.
Figure 5.12
Discrete
Output Connections
*The discrete outputs can be connected to inputs of other
modules provided that the current does not exceed 100mA.
50050
OUTPUT 1
OUTPUT 2
O/P SUPPLY
Wiring Arm
Terminals
36
38
40
LOOP 2
37
39
LOOP 1
OUTPUT 1
OUTPUT 2
LOADS*
5 to 30 VDC
Discrete Output
Supply
(Customer Supplied)
+ -
Ground the shield at
the I/O chassis end.
LOADS*
2
2
2
2
Belden 8761 or equivalent (50 ft. max.)
Connecting the Discrete
Outputs