Message Formats
Appendix A
A12
Unprotected Read
Use this command to read words of data from any area of PC data table
memory. Use the SIZE field to specify the number of bytes to be read.
To specify a number of PC words, SIZE should be an even value because
PC words are two bytes long.
Command Format:
DLE
SRC C
0
S
TNS
MD
1
TS
TNS
STX DLE ETX
BCC
ADDR SIZE
Reply Format:
DLE
SRC C
4
S
TNS
MD
1
TS
TNS ADDR
STX
DLE ETX
BCC
DATA - Max of 244 bytes
Unprotected Write
Use this command to write words of data into any area of PC data table
memory.
Command Format:
DLE
SRC C
0
S
TNS
MD
8
TS
TNS ADDR
STX
DLE ETX
BCC
DATA - Max of 242 bytes
Reply Format:
DLE
SRC C
0
S
TNS
MD
1
TS
TNS
STX DLE ETX
BCC