Message Formats
Appendix A
A27
Table A.B
Contents
of Status DA
T
A for 1775-KA Modules
Byte Meaning
1
Operating status of PLC-3 processor:
Bits 0 to 1:
0 = Program mode
1 = T
est mode
2 = Run mode
Bit 2:
Not used
Bit 3:
0 = Normal
1 = Major processor fault
Bit 4:
0 = Normal
1 = Shutdown requested
Bit 5:
0 = Normal
1 = Shutdown in ef
fect
Bits 6 to 7:
Not used
2 T
ype of station interface:
Bits 0 to 3:
6 = 1775-KA, Data Highway port
7 = 1775-KA, RS-232-C port
Bits 4 to 7:
4 = PLC-3 processor
3
Current context (stored in bits 4 to 7)
4
Thumbwheel number
5,6
Mode control word. The logical address of the mode control word is
E0.0.0.8.