DeviceNet Analog Base Terminal Block Specifications
The following table contains specifications that are common to
all of the blocks in this document. Individual base block
specifications are detailed after this table.
I/O Channel LED Status Indicator
1790D-TN0V2 1790D-TN0C2
Status: Description: Status: Description:
Flashing Green/
Red
Power up Flashing Green/
Red
Power up
Off Off line Off Off line
Off On line and no field
power
Off On line and no field
power
Green DeviceNet
connection and no
field power
Green DeviceNet
connection and no
field power
Green Field power and
open wire
Green Field power and
open wire
Green Field power and valid
output
Green Field power and valid
output
Flashing Red Field power and
output out of range
Flashing Red Field power and
output out of range
Flashing Green Output idle Flashing Green Output idle
Flashing Red Recoverable fault Flashing Red Recoverable fault
Environmental Specifications
Operating Temperature 0 to 55°C (32 to 131°F)
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Storage Temperature -40 to 85°C (-40 to 185°F)
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock)
Relative Humidity 5-90% non-condensing
IEC 60068-2-30 (Test Db, Un-packaged Non-operating)
Operating Altitude 2000m
Specifications continued on next page.