Installing Block I/O
Chapter 3
3-23
Figure 3.17
Input/Output
W
iring Connections for the 17918BR
Series
B
RIO
1
30
PLC and SLC
24V dc
+-
24V dc
+
-
GND
BLU
CLR
in
00
in 01
in 02
in 03
in 04
in 05
in 06
in 07
RET
in
NOT
USED
SHD
out 00
out 02
out 03
out 04
out 05
out 06
out 07
Vac/dc
out
NOT
USED
out 01
+24
RET
+24
RET
in
NOT
USED
12399-I
NOT
USED
RET
in connections are internally connected together
.
V
ac/dc out connections must be externally connected together to accommodate amperage rating.
Output fusing is recommended. Refer to
Table 2.B
on page
28.
NOTE:
29
30
1
2
ac/dc
L1/+
L2N/-
Vac/dc
out
Connections
1791-8BR Series B
Connections
Designation Description Terminal No.
Power
+24 +24V dc Power 1
Power
Connections
RET +24
dc Return 3
GND Chassis ground 2
1
Remote I/O
BLU Blue wire - RIO 6
Remote I/O
Connections
CLR
Clear wire - RIO 8
SHD Shield - RIO 7
I/O Connections
Input
in 00 thru in 07 Input 00 thru 07
16, 18, 20, 22, 24,
26, 28, 30
Input
RET in
dc input Return 12, 14
2
Vac/dc out ac or dc Output Supply 11, 13
3
Output
out 00 thru out 07
Output 00 thru 07
15, 17, 19, 21, 23,
25, 27, 29
Not used
For internal test only; not
for customer use.
4, 5, 9, 10
1
Connect
chassis ground to equipment grounding stud. These are not internally connected.
2
T
erminals 12 and 14 are internally connected.
3
T
erminals 1
1 and 13 must be externally connected by customer to accommodate amperage rating.