ArmorBlock 2 Input/2 Output Module34
Publication 1792-5.5 – October 1996
Specifications
2 Input/2 Output Module – 1792-IB2XOB2E/B
Input Specifications
Inputs per Block 2 sinking
On-state Voltage Range 10–30V dc
On-state Current Maximum
Minimum
6.0mA @ 30V dc
2.0mA @ 10V dc
Off-state Voltage Maximum 5V dc
Off-state Current Minimum 1.5mA
Transition Voltage 5–10V dc
Transition Current 1.5–3.0mA
Input Impedance Maximum 5K ohms
Input Signal Delay Off to On
On to Off
0ms, 2ms, 4ms, 8ms, 16ms
0ms, 2ms, 4ms, 8ms, 16ms
Sensor Source Voltage
Current
10–25V dc
50mA per point, 0.1A total per module
Output Specifications
Outputs per Block 2 sourcing
Output Voltage Range 19 – 30V dc
On-state Voltage Maximum 0.25V dc @ rated current
On-state Current Maximum 2.0A per output @ 70
o
C
Module Current (all outputs on)
Maximum
4.0A per module
1
Off-state Leakage Current
Maximum 1.5mA per output
Surge Current (per output)
Maximum 4.0A for 10ms, repeatable every 2s
Specifications continued on next page