Rockwell-automation 1792D-2BVA2D ArmorBlock MaXum 2 Input with Alarm/2 Instrukcja Użytkownika Strona 9

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 16
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 8
ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B 9
Publication 1792D-IN015B-EN-P - September 2000
The word/bit definitions are explained below.
The DeviceNet Network uses advanced network technology,
producer/consumer communication, to increase network
functionality and throughput. Visit our website at
http://www.ab.com/networks
for producer/consumer technology
information and updates.
Troubleshoot with the Indicators
This module has the following indicators:
Network/Module status indicator
Logic status indicators
Auxiliary power indicators
Individual point status indicators for inputs 0 and 1 and
outputs 0 and 1
Byte Bit Description
Produces 0 00-01
02-03
04
05
06
07
Input status bits: When the bit is set (1), the input is on. Bit
00 = input 0, bit 01= input 1.
Alarm Status bit: Bit 02=Alarm A0, bit 03=Alarm A1.
Input Short Circuit Fault (ISC): ISC-A indicates a short circuit
for input 0.
Input Short Circuit Fault (ISC): ISC-B indicates a short circuit
for input 1.
Input Off Wire Fault (OW): OW-A indicates an off wire fault
for input 0.
Input Off Wire Fault (OW): ISC-B indicates an off wire fault
for input 1.
Produces 1 00-01
02-05
06
07
Output No load or Overload Fault (OFLT): When the bit is set
(1) an output fault has occurred. OFLT0=output 0,
OFLT1=output 1.
Reserved
Output Power Fault (OPWR): When the bit is set (1), Auxiliary
Power is not present.
Reserved
Consumes 0 00-01
02-07
Output bits: When the bit is set (1), the output will be turned
on. Bit 00=output 0, bit 01=output 1.
Reserved
Przeglądanie stron 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Komentarze do niniejszej Instrukcji

Brak uwag