6 ArmorBlock LP2 2 Sinking Input Module
Publication 1792D-5.43 - July 1999
Polled - a master initiates communication by sending its polled I/O
message to the module. The 2 input module scans the inputs producing a
response that reflects their status.
Change of state - productions occur when an input changes. If no input
change occurs within the expected packet rate, a heartbeat production
occurs. This heartbeat production tells the scanner module that the module
is alive and ready to communicate.
Refer to the table below for the word/bit definitions.
Refer to the table below for byte/bit descriptions.
The DeviceNet Network uses advanced network technology, producer/
consumer communication, to increase network functionality and
throughput. Visit our web site at http://www.ab.com/networks
for producer/
consumer technology information and updates.
Bit 0706050403020100
Produces 0 ISC RSVD RSVD RSVD RSVD RSVD I1 I0
Where: ISC = Input Short Circuit RSVD = Reserved I = Input
Byte Bit Description
Produces 0 00-01
07
Input Status bits: When the bit is set (1), the input is on.
Bit 00 = input 0, bit 01 =input 1.
Input Short Circuit (ISC).