2–7Installing Your Remote I/O Adapter Module
Publication 1794ĆUM009D-EN-P - April 2004
Connect external wiring to the remote I/O adapter as shown below.
1
SH
2
BC
D
A
20131
24V
COM
AllenĆBradley
24 VDC
POWER SUPPLY
RIO ADAPTER
1794-ASB
ADAPTER
ACTIVE FAULT
LOCAL
FAULT
Termination resistor (if required)
82or 150(refer to your processor
documentation for size and usage)
PWR
1. Connect the remote I/O cable to the removable plug-in remote
I/O connector.
Connect To
Blue Wire - RIO 1
Shield Wire - RIO SH
Clear Wire - RIO 2
ATTENTION
!
If this is the last adapter in your FLEX I/O
system, or the last adapter on the remote I/O link,
you must use a termination resistor across
terminals 1 and 2 on the remote I/O connector.
Refer to the information supplied with the
processor being used for information on the size
of the resistor.
2. Connect +24V dc input to the left side of the lower connector
terminal A.
3. Connect 24V common to the left side of the upper connector
terminal B.
4. Connections C and D are used to pass 24V dc power and
common to the next module in the series (if required).
Wiring when total current draw is less than 10A
DaisyĆchaining
24V dc
Note: Refer to the individual instructions for each module for actual wiring information.
Note: Modules must be either all analog or all discrete. Do not mix analog
and discrete modules when using the daisyĆchain wiring scheme.
For Example:
Wiring