FLEX I/O 8 Input HART Analog Module 23
Publication
1794-IN108D-EN-P - January 2014
Input Map (Series A Mode)
Word Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 Input Data Channel 0
1
Input Data Channel 1
2 Input Data Channel 2
3 Input Data Channel 3
4 Input Data Channel 4
5 Input Data Channel 5
6 Input Data Channel 6
7 Input Data Channel 7
8OA
Ch 7
OA
Ch 6
OA
Ch 5
OA
Ch 4
OA
Ch 3
OA
Ch 2
OA
Ch 1
OA
Ch 0
UA
Ch 7
UA
Ch 6
UA
Ch 5
UA
Ch 4
UA
Ch 3
UA
Ch 2
UA
Ch 1
UA
Ch 0
9RF
Ch 7
RF
Ch 6
RF
Ch 5
RF
Ch 4
RF
Ch 3
RF
Ch 2
RF
Ch 1
RF
Ch 0
LF
Ch7
LF
Ch6
LF
Ch5
LF
Ch4
LF
Ch3
LF
Ch2
LF
Ch1
LF
Ch0
10 Reserved HR Reserved Diagnostic Status
11 HCF
Ch 7
HCF
Ch 6
HCF
Ch 5
HCF
Ch 4
HCF
Ch 3
HCF
Ch 2
HCF
Ch 1
HCF
Ch 0
HF
Ch 7
HF
Ch 6
HF
Ch 5
HF
Ch 4
HF
Ch 3
HF
Ch 2
HF
Ch 1
HF
Ch 0
12
HT
Ch 7
HT
Ch 6
HT
Ch 5
HT
Ch 4
HT
Ch 3
HT
Ch 2
HT
Ch 1
HT
Ch 0
HC
Ch 7
HC
Ch 6
HC
Ch 5
HC
Ch 4
HC
Ch 3
HC
Ch 2
HC
Ch 1
HC
Ch 0
Where: OA = over alarm
UA = under alarm
RF = remote fault
LF = local fault
HR = HART rebuild
HCF = HART current fault
HF = HART communication fault
HT = HART transmitter list
HC = HART communication