Publication 1794-UM061A-EN-P - July 2006
Configure your Digital Module on an EtherNet/IP Network 87
Ownership
In a Logix5000 system, modules multicast data. This means that multiple
modules can receive the same data at the same time from a single module.
When you choose a communication format, you have to choose whether to
establish an owner or listen-only relationship with the module
If the module is also in the I/O configuration of another controller, then select
the Listen Only version of the Comm Format (for example, Listen Only -
Input Data).
Select a Remote Adapter
The remote adapter you use depends on the distributed I/O you use. When
using FLEX I/O modules, you use the FLEX I/O adapter, cat. no.
1794-AENT, which requires the BOOTP utility.
Owner controller The controller that creates the primary configuration and communication connection to a
module. The owner controller writes configuration data and can establish a connection to
the module.
Listen-only connection An I/O connection where another controller owns/provides the configuration data for the
I/O module. A controller using a listen-only connection only monitors the module. It does
not write configuration data and can only maintain a connection to the I/O module when
the owner controller is actively controlling the I/O module.
An owner connection is any connection that
does not include Listen-Only in its Comm Format.
Listen-only Connection