Publication 1794-UM065B-EN-E - September 2010
Configurable FLEX I/O Analog Module Features 13
Fault Alarm
Fault Alarm selects whether the channel fault detection is enabled or disabled.
There is a 100 Hz (10 ms) filter for wire off or lead break detection.
Use your programming software to set the Fault Alarm. Set the feature bit to 0
to disable the alarm. Set the bit to 1 to enable wire off/lead break fault
detection.
Understand Image Table
Mapping and Bit/Word
Descriptions
All Allen Bradley FLEX I/O modules have a sixteen word table of Real Time
Data (RTD) to be transferred between the controller and the I/O module.
4mA as
4…20 mA
0.1% of
4…20 mA
2…22 mA 2000…22000
(2.000…22.000 mA)
1000/
1.0 µA
Min=2 mA
Max=22 mA
hold
Last=hold
FS value
5 4…20 mA — 4…20 mA Not assigned
6 4…20 mA 4…20 mA Not assigned
7 Unsigned
integer as
4…20 mA
0.03% of
4…20 mA
4…20 mA 0…65535
(4…20 mA)
4095/
0.244 µA
Min=4 mA
Max=20 mA
hold
Last=hold
FS value
8 0…20 mA 0…20 mA Not assigned
9 0…20 mA 0…20 mA Not assigned
10 0…20 mA 0…20 mA Not assigned
11 0…20 mA 0…20 mA Not assigned
12 4…20 mA Not assigned
13 4…20 mA Not assigned
14 % as
4…20 mA
0.16% of
4…20 mA
2…22 mA -1250 … +11250
(2’s complement)
(-12.50% …
+112.50%)
625/
1.6 µA
Min=2 mA
Max=22 mA
hold
Last=hold
FS value
15 4…20 mA 4…20 mA Not assigned
1794-OF8IH Data Formats
Data
Format
Format Resolution Full
Output
Range
Module Data Processing Data Table Value
(Interpretation)
Count per
mA/
Resolution
Analog Fault
State
Output = 16
datatable
(
65535
)
+ 4
Output = 16
datatable
(
10000
)
+ 4