Publication 1794-UM065B-EN-E - September 2010
1794-IF8IH and 1794-OF8IH Configuration 45
Real Time Data (RTD)
Profile, Primary Input
Parameters
Primary Input Data (8 of 16 bits each)
Specifies the value of the input data from the module. Specific format is
controlled by module Data Format Control parameter.
Range: Refer to Data Format (8 of 4 bits) on page 39.
Data Table Reference: input data, Input Words 0…7 (I0…I7), bits 0…15.
Input Map
Word Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 Channel 0 Input Data
1 Channel 1 Input Data
2 Channel 2 Input Data
3 Channel 3 Input Data
4 Channel 4 Input Data
5 Channel 5 Input Data
6 Channel 6 Input Data
7 Channel 7 Input Data
8 H7H6 H5H4H3H2H1H0L7 L6 L5 L4 L3 L2 L1 L0
9 R7R6 R5R4R3R2R1R0P7 P6P5P4 P3P2P1 P0
10
11 C7 C6 C5 C4 C3 C2 C1 C0 F7 F6 F5 F4 F3 F2 F1 F0
12 X7 X6 X5 X4 X3 X2 X1 X0 Reserved
Where: Hn: Channel n High Alarm
Ln : Channel n Low Alarm
Rn : Channel n Out of Range Alarm
Pn : Channel n Second (Remote) Alarm
Fn : Channel n HART Failure
Cn : Channel n HART Current Fault
Xn : Channel n HART Transmitter Present