Rockwell Automation Publication 193-UM011A-EN-P - September 2010 61
Programmable Parameters Chapter 5
Advanced Setup Group
TRIP ENABLE
This parameter allows the installer to enable
or disable trip functions separately. Overload,
Phase Loss, and Comm Fault are enabled
from the factory.
1 = Enabled
0 = Disabled
Parameter Number 24
Access Rule Get/Set
Data Type WORD
Object Mapping 0x29-1-124
Group Advanced Setup
Units
Minimum Value 0000000000000000
Maximum Value 1111111111111111
Default Value 0000000000000000
Bit Function:
1514131211109876543210
X Ground Fault
X L1 Undercurrent
X L2 Undercurrent
X L3 Undercurrent
X L1 Overcurrent
X L2 Overcurrent
X L3 Overcurrent
X L1 Loss
X L2 Loss
X L3 Loss
X Comm Fault
X Comm Idle
X Remote Trip
WARNING ENABLE
This parameter allows the installer to enable
or disable warning functions separately. All
warning functions are disabled from the
factory.
1 = Enabled
0 = Disabled
Parameter Number 25
Access Rule Get/Set
Data Type WORD
Object Mapping 0x29-1-125
Group Advanced Setup
Units
Minimum Value 0000000000000000
Maximum Value 1111111111111111
Default Value 0000000000000000