Chapter 6 Current Monitoring Parameters
Ground Fault Current
Reporting
Current Range
The following chart illustrates the minimum and maximum reporting ground
fault current values for a given ground fault current range.
The EC4 Current Monitoring Relay will report 0 A if the ground fault current is below 50% of the minimum
ground fault current setting for a given range.
The EC4 Current Monitoring Relay is capable of reporting values greater than the maximum values shown, but
the accuracy of the value is compromised.
The accuracy specified is only applicable to non-distorted sinusoidal currents.
20…100 mA for resistive loads only. For motor loads consult your local Allen-Bradley distributor.
Frequency Range
The EC4 Current Monitoring Relay is capable of sensing variable frequency
ground fault currents ranging from 20…250 Hz.
Exception: Any EC4 Current Monitoring Relay using an external ground fault
sensor is limited to 50/60 Hz detection.
Monitor Group
Table 22 - Ground Fault Current Reporting Summary
Ground Fault
Current Range
Minimum
Reporting
Current ➊➌
Maximum
Reporting
Current ➋➌
E3 Plus Cat. No. /Series
20…100 mA 10 mA 180 mA 193/592-EC3 — Series C and later
100…500 mA 50 mA 900 mA 193/592-EC3 — Series C and later
200 mA…1.0 A 100 mA 1.80 A 193/592-EC3 — Series C and later
1.0…5.0 A 500 mA 9.00 A 193/592-EC2 — Series A and later
L1 CURRENT
This parameter provides the L1 phase current
measurement in amperes.
Parameter Number 1
Access Rule Get
Data Type INT
Object Mapping 2C
hex
-1-231
2C
hex
-1-8
2C
hex
-1-227
Group Monitor
Units Amps
Minimum Value See Table 20 -
Maximum Value See Table 20 -
Default Value None