A-24 DeviceNet Information
Publication 198-UM002A-EN-P December 2001
I/O Assembly Instance Summary
These assemblies are intended for use when the “Motor Starter Type” attribute in the DeviceNet Interface
object is set to a value greater than zero. This results in the MDSA reporting a Device Type of 22 (Motor
Starter). For a complete description of these I/ O assemblies and a complete description of “Motor Starter
Type” operation, refer to Appendix B.
Table A.44
Instance Type Size (bytes) Description
3 Consumed 1 ODVA Starter Profile output assembly
52 Produced 1 ODVA Starter Profile input assembly
100 Consumed (Modules+1) / 2 “Nibble-wise” output assembly
101 Produced (Modules+5) / 2 “Nibble-wise” input assembly
102 Consumed I/O modules Modular “Byte-wise” output assembly for 198-DNG
103 Produced I/ O modules + 2 ModularByte-wise input assembly for 198-DNG
104 Consumed 6 Default “Byte-wise” output assembly for 198-DNG
105 Produced 8 Default “Byte-wise” input assembly for 198-DNG
106 Consumed 16 Default “Byte-wise output assembly for 198-DN
107 Produced 20 Default “Byte-wise” input assembly for 198-DN
110 Consumed 8 Un-fragmented “Byte-wise” DeviceLogix output
assembly for 198-DNG
111 Consumed 10 Fragmented “Byte-wise” DeviceLogix output assembly
for 198-DNG
112 Consumed 20 “Byte-wise” DeviceLogix output assembly for 198-DN
120 Produced 0…16 Custom Parameter Based input assembly
121 Consumed 0…8 Custom Parameter Based output assembly
150 Consumed 2 Default Distributed Starter output assembly
151 Produced 5 Default Distributed Starter input assembly
152 Consumed 2 Default Reversing Distributed Starter output assembly
153 Produced 5 Default Reversing Distributed Starter input assembly
154 Consumed 2 Default Inverter Type Distributed Starter output
assembly
155 Produced 5 Default Inverter Type Distributed Starter input
assembly
156 Consumed 2 Default Soft Start Type Distributed Starter output
assembly
157 Produced 5 Default Soft Start Type Distributed Starter input
assembly
180 Produced 2 Hardware Inputs 116
181 Produced 2 Hardware Inputs 1732
182 Produced 2 Hardware Input Fault Status 116
183 Produced 2 Hardware Input Fault Status 1732
184 Consumed 2 Hardware Outputs 116
185 Consumed 2 Hardware Outputs 17…32
186 Consumed 2 Consumed Network Bits 116
187 Consumed 2 Consumed Network Bits 1732
188 Produced 2 Produced Network Bits 115
189 Produced 2 DeviceNet Status Bits
190 Produced 2 Module Status Bits 116