Parameter Access Level
Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013 127
The operator first views the Start owner to be certain that the Start button on the
HIM is issuing a command.
Start Owner
When the local Start button is pressed, the display indicates that the command is
coming from the HIM.
Start Owner
The [Start Owner] indicates that there is not any maintained Start commands
causing the drive to run.
Stop Owner
The operator then checks the Stop Owner. Notice that bit 0 is a value of “1,
indicating that the Stop device wired to the Digital Input terminal block is open,
issuing a Stop command to the drive.
Until this device is reclosed, a permanent Start Inhibit condition exists and the
drive will not restart.
Also refer to Start Inhibits
and Start Permissives.
Parameter Access Level The PowerFlex 70 allows the user to restrict the number of parameters that are
viewable on the LCD or LED HIM. By limiting the parameter view to the most
commonly adjusted set, additional features that may make the drive seem more
complicated are hidden.
If you are trying to gain access to a particular parameter and the HIM skips over
it, you must change the parameter view from “Basic” to “Advanced.” This can be
accomplished in two different ways:
Press “Alt” and then View” from the HIM and change the view.
or
Reprogram Parameter 196 [Param Access Lvl] to “Advanced”.
00000000
Adapter # X6543210
00000010
Adapter # X6543210
00000001
Adapter # X6543210