CE Conformity
64 Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013
Table 5 PowerFlex 70 – EN61800-3 EMC Compatibility
Table 6 PowerFlex 70 – EN61800-3 First Environment Restricted Distribution
)
Table 7 PowerFlex 700 EN61800-3 EMC Compatibility
(1)
(1) External filters for First Environment installations and increasing motor cable lengths in Second Environment
installations are available. Roxburgh models KMFA (RF3 for UL installations) and MIF or Schaffner FN3258
and FN258 models are recommended. Refer to Table 8
and http://www.deltron-emcon.com and http://
www.mtecorp.com (USA) or http://www.schaffner.com, respectively.
(2) Two turns of the blue comm option cable through a Ferrite Core (Frames A, B, C Fair-Rite #2643102002, Frame
D Fair-Rite #2643251002 or equivalent).
(3) Refer to the 1321 Reactor and Isolation Transformer Technical Data publication, 1321-TD001x for 1321-Mxxx
selection information.
Frame
Drive Description
Second Environment
Restrict Motor Cable
to 40 m (131 ft.)
Internal Filter
Option
External
Filter
(1)
Input
Ferrite
(2)
ADrive Only
Drive with any Comm Option
Drive with Remote I/O ✔✔
BDrive Only ✔✔––
Drive with any Comm Option ✔✔––
Drive with Remote I/O ✔✔
CDrive Only ––
Drive with any Comm Option ––
Drive with Remote I/O ––
DDrive Only ––
Drive with any Comm Option ––
Drive with Remote I/O ––
EDrive Only ––
Drive with any Comm Option ––
Drive with Remote I/O ––
Frame
Drive Description
First Environment Restricted Distribution
Restrict Motor
Cable to:
Internal
Filter Option
External
Filter
(1)
Comm Cable
Ferrite
(2)
Common Mode
Core
(3)
A Drive Only 40 m (131 ft.) ––
Drive with any Comm Option 40 m (131 ft.) ––
Drive with Remote I/O 40 m (131 ft.) ✔✔
BDrive Only 12 m (40 ft.) ––
Drive with any Comm Option 12 m (40 ft.) ––
Drive with Remote I/O 12 m (40 ft.)
C Drive Only 12 m (40 ft.)
Drive with any Comm Option 12 m (40 ft.)
Drive with Remote I/O 12 m (40 ft.) ✔✔
DDrive Only 12 m (40 ft.)
Drive with any Comm Option 12 m (40 ft.)
Drive with Remote I/O 12 m (40 ft.)
E Drive Only 30 m (98 ft.) ––
Drive with any Comm Option 30 m (98 ft.) ––
Drive with Remote I/O 30 m (98 ft.) ✔✔
Frame
Second Environment
Restrict Motor Cable to 30 m (98 ft.)
First Environment Restricted Distribution
Restrict Motor Cable to 150 m (492 ft.)
Any Drive and Option Any Drive and Option External Filter Required
0-6 ✔✔