Rockwell-automation 2705 REDIPANEL KEYPAD MODULE USER MANUAL Instrukcja Użytkownika

Przeglądaj online lub pobierz Instrukcja Użytkownika dla Ekwipunek Rockwell-automation 2705 REDIPANEL KEYPAD MODULE USER MANUAL. Rockwell Automation 2705 REDIPANEL KEYPAD MODULE USER MANUAL User Manual Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 93
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 0
User
Manual
Bulletin 2705
RediPANEL
Keypad
Modules
(Cat. Nos. 2705-K11C1,
-K11C2, -K12C2, -K12C3,
-K12C4)
Allen-Bradley
Przeglądanie stron 0
1 2 3 4 5 6 ... 92 93

Podsumowanie treści

Strona 1 - Allen-Bradley

UserManualBulletin 2705RediPANELKeypadModules(Cat. Nos. 2705-K11C1,-K11C2, -K12C2, -K12C3,-K12C4)Allen-Bradley

Strona 2 - • recognize the consequences

Chapter 2Product Introduction2–3The 2705 RediPANEL Keypad Module features a numeric keypad withDELETE, ENTER, decimal and polarity keys. Using the key

Strona 3 - Chapter 4

Chapter 2Product Introduction2–42) A combination of ASCII and numeric data. Up to 8 characters of ASCII data are displayed on the left side of the di

Strona 4 - Chapter 7

A–B3Chapter3–1Installing the Bulletin 2705 Keypad ModuleThis chapter lists electrical precautions and power and groundingrequirements for installing t

Strona 5 - Appendix

Chapter 3Installing the Bulletin 2705 Keypad Module3–2Grounding is an important safety measure in electrical installations. Withsolid state systems,

Strona 6 - Using this Manual

Chapter 3Installing the Bulletin 2705 Keypad Module3–3Figure 3.1 shows recommended spacing for modules inside the NEMAenclosure.Figure 3.1Spacing for

Strona 7 - Definition of Major Terms

Chapter 3Installing the Bulletin 2705 Keypad Module3–4To install the module, follow these guidelines:Step 1 -Cut an opening in the panel approximately

Strona 8 - Product Introduction

Chapter 3Installing the Bulletin 2705 Keypad Module3–5Step 4 -To complete the mechanical installation, apply the mounting brackets and tighten all the

Strona 9 - Applications

Chapter 3Installing the Bulletin 2705 Keypad Module3–6Connect the Keypad Module to the scanner module with Allen–Bradley I/Ocable (Catalog No. 1770–CD

Strona 10 - Information Display

A–B4Chapter4–1Configuring the Bulletin 2705 Keypad Modulewith PLC ControllersThis chapter lists compatibility considerations for operating the Bulleti

Strona 11 - Remote I/O Communications

with PLC ControllersChapter 4Configuring the Bulletin 2705 Keypad Modules4–2The following diagrams show applications using the Bulletin 2705 KeypadMod

Strona 12 - • 18–30 Volts DC

Solid state equipment has operational characteristics differing from those ofelectromechanical equipment. “Safety Guidelines for the Application,Insta

Strona 13 - NEMA Enclosures

with PLC ControllersChapter 4Configuring the Bulletin 2705 Keypad Module4–3Remote I/O Architecture (continued)Figure 4.3Keypad Module with PLC–3Scanne

Strona 14 - Mechanical Installation

with PLC ControllersChapter 4Configuring the Bulletin 2705 Keypad Modules4–4Figure 4.5Keypad Module with PLC–5/15, 5/25PLC–5/15PLC–5/25ScannerPort1785

Strona 15 - Step 3

with PLC ControllersChapter 4Configuring the Bulletin 2705 Keypad Module4–5Figure 4.7Keypad Module with SLC–5/02SLC–5/02RIOScannerPort1747–SNKeypadKey

Strona 16 - Step 4

with PLC ControllersChapter 4Configuring the Bulletin 2705 Keypad Modules4–6Table 4.BApplicable Programmable Controllers Requiring 1771-SN Sub-scanner

Strona 17 - Connecting a Scanner Module

with PLC ControllersChapter 4Configuring the Bulletin 2705 Keypad Module4–7The 2705 Keypad Module can be configured for any of four rack sizes: 1/4,1/

Strona 18 - Communications

with PLC ControllersChapter 4Configuring the Bulletin 2705 Keypad Modules4–8Once you have selected the appropriate scanner for the PLC controller, Tab

Strona 19 - Remote I/O Architecture

A–B5Chapter5–1Selecting OptionsThis chapter describes DIP switch location and functions on the Bulletin2705 RediPANEL Keypad Module. It also lists th

Strona 20 - PLC–3/10

Chapter 5Selecting Options5–2The following figures show examples of DIP switch settings. Figure 5.2illustrates the “ON” and “OFF” positions of the DI

Strona 21

Chapter 5Selecting Options5–3Figure 5.4 lists the rack address settings on Switch Bank #1 for PLC–3,PLC–5/15, PLC–5/25 and SLC–5/02 controllers.Figure

Strona 22 - Scanners

Chapter 5Selecting Options5–4Figure 5.5 gives the switch functions and settings for switch bank #2. Figure 5.5Setting Switch Bank #2ONOFFONOFFSW–2ONO

Strona 23

A–BRediPANEL Keypad ModulesUser ManualTable of ContentsiChapter 1Chapter Objectives 1–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strona 24 - Calculating Rack Size

Chapter 5Selecting Options5–5Figure 5.6 gives the switch functions and settings for Switch Bank #3. Theseswitch bank #3 settings are for all PLC’s.

Strona 25 - Remote I/O Configuration

A–B6Chapter6–1Operating ModesThis chapter describes the operating modes of the Bulletin 2705 RediPANELKeypad Module. Topics include:• PLC output disp

Strona 26 - Selecting Options

Chapter 6Operating Modes6–2Numeric DataNumeric data appears on the right–hand side of the display in the eightright–most character positions. These

Strona 27 - Setting Switch Bank #1

Chapter 6Operating Modes6–3The Keypad Module offers a standard numeric keypad interface with apolarity (minus sign) key and a decimal point as shown i

Strona 28 - Rack 00 not valid with PLC–5s

Chapter 6Operating Modes6–4To enter data you must first key in the desired numbers using the numerickeypad. The data will appear on the right hand si

Strona 29 - Setting Switch Bank #2

Chapter 6Operating Modes6–5.Figure 6.3Display for Destination EntryThe keypad operator starts by pressing the ENTER key. The presentdestination is di

Strona 30 - Setting Switch Bank #3

Chapter 6Operating Modes6–6The Message Editor inside the module is accessed by the keyboard when anykey is depressed. A prompt appears on the display

Strona 31 - Operating Modes

Chapter 6Operating Modes6–7The procedure for entering messages into the module is interactive:Step 1 - Remove power before plugging keyboard into the

Strona 32 - ASCII Message Display

Chapter 6Operating Modes6–8The editing commands are single key strokes:Left arrow (←)-Move cursor one position to the left.Right arrow(→)-Move cursor

Strona 33 - Data Entry

A–B7Chapter7–1ProgrammingThis chapter describes the process of creating a program for the Bulletin2705 RediPANEL Keypad module. The detailed listing

Strona 34 - Destination Entry

RediPANEL Keypad ModuleUser ManualTable of ContentsiiChapter 5Chapter Objectives 5–1DIP Switches 5–1Typical Switch Settings 5–2Setting Switch Bank #1

Strona 35 - • IBX–XT/AT style keyboard

Chapter 7Programming7–2The PLC–5 programming examples given on the following pages are basedon the system configuration listed below.Note – System con

Strona 36

Chapter 7Programming7–3Figure 7.1 below shows the Input and Output Image Tables for the systemconfiguration described on Page 2.Figure 7.1Integer Mode

Strona 37 - Entering Messages

Chapter 7Programming7–4Figure 7.2Rung 2:0F1FunctionKeyI:020] [10F1FunctionKeyI:020] [Rung 2:110COUNT UPCounter C5:1Preset 69Accum 50CTU(CU)(DN)MOVSo

Strona 38 - Editing Commands

Chapter 7Programming7–5The Keypad Module is not only capable of displaying numeric data, but alsoalphanumeric messages to describe that data. These m

Strona 39 - Programming

Chapter 7Programming7–6Rung 2:2 shows how the same input, F1, which is used to move theaccumulated value of the counter to the Keypad display, can als

Strona 40 - System Configuration

Chapter 7Programming7–7In Figure 7.4, function key F3 is used to initiate a MOVE instruction. TheMOVE instruction, moves the constant 3 to the Keypad

Strona 41

Chapter 7Programming7–8Figure 7.5Rung 2:51116MOVMOV16F2FunctionKeyI:020] [Rung 2:6MOVSource I:02150Dest C5:1.PRE69MOVSource 2Dest 0:0222MOVSource C5:

Strona 42 - Displaying Numeric Data

Chapter 7Programming7–9The keypad destination function can be used to load data values into multipletimer/counter presets or other PLC memory location

Strona 43 - Describe Data

Chapter 7Programming7–10Rungs 3–16:Would appear the same but with different timer/destination bit addresses.Rung 17:Destination bit I:024/00 is “ON” w

Strona 44 - Displaying a Full Line Stored

Chapter 7Programming7–11A 1771–SN, Sub I/O scanner may be used with a PLC–5 family processorwhen the application requires more remote devices than tha

Strona 45 - CHARACTER MSG.”

RediPANEL Keypad ModuleUser ManualTable of ContentsiiiInstruction Parameters 7–12Programming Example 7–13Programming Example 7–15PLC–2 Programming Exa

Strona 46 - Figure 7.5

Chapter 7Programming7–12The ladder diagram in Figure 7.6 is a simple programming example showingBidirectional Block Transfers between a sub I/O scanne

Strona 47

Chapter 7Programming7–13be reflected in this file. Therefore, all your input or output addresses forthese remote devices will be elements of this fil

Strona 48

Chapter 7Programming7–14Figure 7.7PLC–5/15 and Sub I/O Scanner Programming ExamplePLC5/151771–SN(Sub I/O Scanner)1771–I/O(Remote 1)1771–I/O(Remote 2)1

Strona 49 - Sub I/O Scanner with Keypad

Chapter 7Programming7–15In the programming example shown in Figure 7.7, you’ll notice the lengthhas been set for (12), 8 words for the block transfer

Strona 50

Chapter 7Programming7–16The following pages contain a PLC–2 example program which utilizes manyof the functions of the Keypad Module. Keep in mind th

Strona 51

Chapter 7Programming7–17The example program below is explained on the following pages. We present the program here (and on the next page)in its entire

Strona 52 - 012 4365701 2 43657 01243657

Chapter 7Programming7–18!! +731011(L)54000!!!! +00( CTU)04120137500G8540214 +00( PUT)04130515002G!!540003!! +00( PUT)01370312G54031016000109!! +16( PU

Strona 53

Chapter 7Programming7–19Rungs A, B and C set the program up:! +++BLOCK XFER READDATA ADDR: 0030MODULE ADDR: 111BLOCK LENGTH 14FILE: 0200–0215+++ +!!!!

Strona 54 - PLC-2 Programming Example

Chapter 7Programming7–20– – – –Figure 7.9I/O Table for Sample Program: BCD Mode, 3/4 RackWord 410Word 413Word 412Word 411Word 313Word 312Wo

Strona 55 - PLC–2 Programming Example

Chapter 7Programming7–21Rungs 1–5 show a procedure for monitoring the accumulated value ofcounter 037 using the Keypad Module:!!!!!!!!!!!!!!!!!!! +310

Strona 56

1Chapter1–1Using this ManualThis chapter describes the manual’s organization, intended audience, andspecial terminology.This manual describes the equi

Strona 57 - Program Set-up

Chapter 7Programming7–22Rungs 7–12 show a programming procedure that will allow you to changethe preset values of the counter that was being monitored

Strona 58 - – – – –

Chapter 7Programming7–23Rungs 13 - 17 retrieve and display a message: +15( PUT)04130511001G13310001!! +1431015( L)41016!!++!!Rung 13:When function key

Strona 59 - Accumulated Value of Counter

Chapter 7Programming7–24In Part A and B we learned how to examine information from the PLC byusing the Keypad. In order to have an 8–character messag

Strona 60

Chapter 7Programming7–25The figures on the following pages show the input and output tables for theKeypad Module.The following symbols and abbreviatio

Strona 61 - 16–Character Message for

Chapter 7Programming7–26Dec. Pos.DECimal POSition. The decimal position field holds a binary value (1–7) that is the number of positions to the right

Strona 62

Chapter 7Programming7–27 Figure 7.10Example of Decimal Point ControlEntered data has 1place to the rightSDPDCSDP is EnabledDec. Pos.Displayed data ha

Strona 63 - I/O Image Tables

Chapter 7Programming7–28RediPANEL Modules have a standard TIMED feature that holds all pushbutton depressions for a minimum of 100 milliseconds to all

Strona 64 - Decimal Point Control

Chapter 7Programming7–29With the handshake feature enabled and the handshake rung in the user’sprogram, the RediPANEL module holds all function key in

Strona 65 - 0 0 1F1

Chapter 7Programming7–30Integer Data – With Stored Message1/2, 3/4 and Full RackFigure 7.13Integer Mode, 1/2, 3/4 and Full Rack with Stored Message D

Strona 66 - When to Use the Handshake

Chapter 7Programming7–31BCD Data – With Stored Message3/4 and Full RackFigure 7.14BCD Mode, 3/4 and Full Rack with Stored Message Display16Word 0Word

Strona 67 - PLC Scan Cycle

Chapter 1Using this Manual1–2To get maximum benefit from this manual and the best use of the Bulletin2705 Keypad Module in your system, you must be ab

Strona 68

Chapter 7Programming7–32Binary Data – With Stored Message1/2, 3/4 and Full RackFigure 7.15Binary Mode, 1/2, 3/4 and Full Rack with Stored Message Dis

Strona 69

Chapter 7Programming7–33Integer Data – With Stored Message1/2, 3/4 and Full RackFigure 7.16Integer Mode, 1/2, 3/4 and Full Rack16Word 0Word 3Word 2Wor

Strona 70

Chapter 7Programming7–34Integer Data – With Stored Message1/4 RackDestination1617DML6L3L415Integer DataHFigure 7.17Integer Mode, 1/4 RackL5L1 S Dec. P

Strona 71 - Input and Output Image Tables

Chapter 7Programming7–35Binary Data – With Stored Message 3/4 and Full RackFigure 7.18BCD Mode, 3/4 and Full Rack16Word 0Word 3Word 2Word 1Word 3Word

Strona 72

Chapter 7Programming7–36Binary Data – With Stored Message1/4 RackFigure 7.19BCD Mode, 1/4 Rack012345671011121314151617H EN F6 F5 F4 F3 F2 F1 BCD1 (MSD

Strona 73

Chapter 7Programming7–37Binary Data – No Stored Message1/2, 3/4 and Full RackFigure 7.21Binary Mode, 1/2, 3/4 and Full Rack16Word 0Word 3Word 2Word 1

Strona 74

Chapter 7Programming7–38Binary Data – No Stored Message1/4 RackFigure 7.22Binary Mode, 1/4 Rack012345671011121314151617HEN F6 F5 F4 F3 F2 F1 S Dec. Po

Strona 75

Chapter 7Programming7–39In the following example, a Bulletin 2705 RediPANEL displays storedmessages. An alarm, connected to an output module, signals

Strona 76

Chapter 7Programming7–40The scanner input file is shown below. The output file is similar, it isaddressed O:1.0 to O:1.3.Bit Number 15 14 13 12 11 10

Strona 77 - Examples

Chapter 7Programming7–41The addresses for the Input and Output files are provided in an octal format.You must convert the bit addresses to decimal to

Strona 78

A–B2Chapter2–1Product IntroductionThis chapter describes the features, functions and operation of the Bulletin2705 RediPANEL Keypad Module.The Bulleti

Strona 79 - Scanner Configuration

Chapter 7Programming7–42The example program is shown below. Each time a function key is pressedon the RediPANEL, its associated message is displayed.

Strona 80 - Example Program

A–B8Chapter8–1Maintenance and TroubleshootingThis chapter describes how to use the Comm/Fault LED indicators, andexplains the power–up sequence error

Strona 81 - • Check for valid data type

Chapter 8Maintenance and Troubleshooting8–2The COMM IndicatorAny communication faults or errors are indicated by the green LED labeledCOMM. The LED c

Strona 82 - Questions

Chapter 8Maintenance and Troubleshooting8–3• Have you changed the settings of any of the DIP switches? New DIPswitch settings will not be acknowledge

Strona 83 - Chapter 8

A–B9Chapter9–1SpecificationsThis chapter lists the specifications for the Bulletin 2705 Keypad Module.FUNCTIONProvides keypad interface for data entry

Strona 84

Chapter 9Specifications9–2Baud Rates:Selectable. 230.4K baud (2500 ft), 115.2K baud (5000 ft) or 57.6K baud(10,000 ft)Interconnect: 3–terminal plug

Strona 85 - Chapter 9

A–BAAppendixA–1Appendix AThis appendix describes the error messages displayed by the KeypadModule. It also lists the display characters and their cor

Strona 86 - Appendix A

Appendix AA–2OVERFLOWThis error indicates that the user attempted to enter a number that was larger than what the module’s configuration could handle.

Strona 87

Appendix AA–3Figure A.1 shows the 14–segment character set for the module display. Thenumbers next to each figure are the hexadecimal values for the c

Strona 88 - Display Characters

A–BIndexI–1AAddress, Rack, 5-1, 5-2Applicable PLCs and Scanners, 4-2Applications, Keypad Module, 2-2Architecture, Remote I/O, 4-2ASCII Data, 2-3, 6-2A

Strona 89

Chapter 2Product Introduction2–2The Keypad Module combines the functions of standard thumbwheel or pushbutton devices with the built–in capabilities o

Strona 90

IndexI–2Entering Messages, 6–7Editing, 6–7Editing Commands, 6–8Storing, 6–7Entering or Changing Data, 7–7EPROM CRC ERROR, A–1Error Messages, A–1BAD MS

Strona 91

IndexI–3Message, Display, 7–25Message Display, ASCII, 6–2Message Editor, 6–6MESSAGE ERROR, A–2Messages, 6–5ASCII Display, 6–2Editing, 6–7Entering, 6–7

Strona 92

IndexI–4Handshake, 2–4, 5–4Keyswitch, 2–4, 5–4Last Device, 5–4Last State, 2–4, 5–4Switch Bank #3Keyboard Style, 5–5SMD and Destination Format,5–5Split

Strona 93 - Worldwide representation

Rockwell Automation helps its customers receive a superior return on their investment by bringingtogether leading brands in industrial automation, cre

Komentarze do niniejszej Instrukcji

Brak uwag